Firstpower Tech. Co., Ltd.
Firstpower Tech. Co., Ltd.
Energizer Rechargeable Batteries
  • Energizer Rechargeable Batteries
Energizer Rechargeable Batteries

Energizer Rechargeable Batteries

Payment Type:
L/C, T/T, D/P
Incoterm:
FOB, CFR, CIF
Min. Order:
100 Piece/Pieces
Min. Order:
100 Piece/Pieces
Delivery Time:
30 Days
Transportation:
Ocean, Land
Quantity:

Your message must be between 20 to 2000 characters

Contact Now
Basic Info
Basic Info
Place of Origin: china
Productivity: 2000, 000kvah/ Year
Supply Ability: 2000, 000kvah/ Year
Payment Type: L/C,T/T,D/P
Incoterm: FOB,CFR,CIF
Certificate: iso,UL,CE
Transportation: Ocean,Land
Product Description
Product Description
FP12180T is a typical back-up power battery desgined for High Temperature application   with  average temperature of 30-35°C or higher during hot season, even the temperature is even higher and can go up to 50 °C inside the telecom cabinet.  




Specifications

Nominal Voltage

12 V

Capacity

(25)

20HR(10.5V) 

18Ah

10HR(10.5V)

16.7Ah

1HR(9.60V)

11.7Ah

Dimension

Length

181±2mm (7.13inch)

Width

77±1mm (3.03inch)

Height

167±2mm (6.57inch)

Total Height

167±2mm (6.57inch)

Approx. Weight

5.45kg (12.0lbs)±4%

Terminal type

T3/T8

Internal resistance

(Fully charged, 25)

Approx. 16mΩ

Capacity affected by temperature (20HR)

40

102%

25

100%

0

85%

-15

65%

Self-discharge

(25)

3 month

Remaining Capacity: 91%

6 month

Remaining Capacity: 82%

12 month

Remaining Capacity: 65%

Nominal operating temperature

25±3(77℉±5℉)

Operating temperature range

Discharge

-15~70(5℉~158)

Charge

-10~70(14℉~158)

Storage

-20~70(-4℉~158)

Float charging voltage(25)

13.60 to 13.80V

Temperature compensation:

-18mV/

Cyclic charging voltage(25)

14.50 to 14.90V

Temperature compensation:

-30mV/

Maximum charging current

5.4A

Terminal material

Copper

Maximum discharge current

270A(5 sec.)

Designed floating life(20)

5~7 years

◆ Absorbent glass mat technology;

◆ Recognized by UL & CE;

◆ ABS container.




Constant Current Discharge Characteristics (A, 25)

F.V/TIME

10min

15min

30min

60min

2h

3h

4h

5h

8h

10h

20h

9.60V

41.9

33.5

18.7

11.7

6.39

4.59

3.67

3.12

2.02

1.70

0.91

9.90V

40.6

32.7

18.3

11.5

6.36

4.56

3.65

3.10

2.01

1.69

0.91

10.2V

39.0

31.5

17.8

11.2

6.30

4.53

3.63

3.08

1.99

1.68

0.91

10.5V

37.3

30.4

17.3

11.0

6.21

4.50

3.60

3.06

1.98

1.67

0.90

10.8V

35.2

28.8

16.7

10.7

6.05

4.37

3.49

2.97

1.92

1.64

0.88

Constant Power Discharge Characteristics (Watt, 25) 

F.V/TIME

10min

15min

30min

60min

2h

3h

4h

5h

8h

10h

20h

9.60V

473

382

214

135

74.8

54.5

43.7

37.3

24.2

20.4

11.0

9.90V

458

373

210

133

74.4

54.2

43.5

37.0

24.1

20.3

10.9

10.2V

440

359

204

130

73.7

53.8

43.2

36.8

23.9

20.2

10.9

10.5V

421

347

199

127

72.6

53.5

42.9

36.5

23.8

20.1

10.8

10.8V

397

329

191

124

70.8

51.9

41.6

35.4

23.0

19.7

10.6

Note: The above characteristics data can be obtained within three charge/discharge cycles.





 



International certifications:
ISO9001 approval, FN: Q3105105131
ISO14001 CTC04912E10302ROM
OHS MS18001 04912S10150ROM
UL approval, FN:MH28204
CE approval, FN:G2M20201-0102-E-16
KS approval, FN:KS C 8519
VDS approval

BS approval


Typical Applications
Fire alarm systems
Solar lighting equipment
Outdoor telecommunication equipment


Send your message to this supplier

  • Ms. SALES

  • Enter between 20 to 4,000 characters.