Specifications
Nominal Voltage |
6 V |
||
Capacity (25℃) |
10HR(5.40V) |
200 Ah |
|
5HR(5.25V) |
175Ah |
||
1HR(4.80V) |
124Ah |
||
Dimension |
Length |
321±2mm (12.64inch) |
|
Width |
176±2mm (6.93inch) |
||
Height |
226±2mm (8.90inch) |
||
Total Height |
T5: 246±2mm (9.69inch) |
||
T11: 229±2mm (9.02inch) |
|||
Approx. Weight |
32kg (70.6lbs)±4% |
||
Terminal type |
T5/T11 |
||
Internal resistance (Fully charged, 25℃) |
Approx. 2mΩ |
||
Capacity affected by temperature (10HR) |
40℃ |
102% |
|
25℃ |
100% |
||
0℃ |
85% |
||
-15℃ |
65% |
||
Self-discharge (25℃) |
3 month |
Remaining Capacity: 91% |
|
6 month |
Remaining Capacity: 82% |
||
12 month |
Remaining Capacity: 65% |
||
Nominal operating temperature |
25℃±3℃(77℉±5℉) |
||
Operating temperature range |
Discharge |
-15℃~70℃(5℉~158℉) |
|
Charge |
-10℃~70℃(14℉~158℉) |
||
Storage |
-20℃~70℃(-4℉~158℉) |
||
Float charging voltage(25℃) |
6.75 to 6.90V Temperature compensation: -9mV/℃ |
||
Cyclic charging voltage(25℃) |
7.25 to 7.45V Temperature compensation: -15mV/℃ |
||
Maximum charging current |
60A |
||
Terminal material |
Copper |
||
Maximum discharge current |
1600A(5 sec.) |
||
Designed floating life(20℃) |
12 years |
◆ Absorbent glass mat technology;
◆ Recognized by UL & CE;
◆ ABS container.
Constant Current Discharge Characteristics (A, 25℃)
F.V/TIME |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
4.80V |
323 |
196 |
124 |
73.1 |
51.0 |
41.8 |
35.7 |
31.2 |
24.5 |
20.4 |
10.7 |
4.95V |
316 |
192 |
122 |
72.6 |
50.7 |
41.6 |
35.5 |
31.0 |
24.3 |
20.3 |
10.7 |
5.10V |
304 |
186 |
119 |
72.0 |
50.4 |
41.3 |
35.2 |
30.8 |
24.2 |
20.3 |
10.6 |
5.25V |
294 |
182 |
117 |
70.9 |
50.0 |
41.0 |
35.0 |
30.6 |
24.0 |
20.1 |
10.6 |
5.40V |
278 |
175 |
113 |
69.1 |
48.5 |
39.8 |
34.0 |
29.7 |
23.3 |
20.0 |
10.5 |
Constant Power Discharge Characteristics (Watt, 25℃)
F.V/TIME |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
4.80V |
1775 |
1100 |
707 |
423 |
300 |
246 |
211 |
184 |
145 |
122 |
64.1 |
4.95V |
1733 |
1078 |
696 |
421 |
298 |
244 |
210 |
183 |
145 |
121 |
64.0 |
5.10V |
1669 |
1045 |
679 |
417 |
296 |
243 |
208 |
182 |
144 |
121 |
63.8 |
5.25V |
1612 |
1019 |
665 |
411 |
294 |
241 |
207 |
181 |
143 |
120 |
63.4 |
5.40V |
1527 |
982 |
645 |
400 |
285 |
234 |
201 |
175 |
138 |
119 |
63.0 |
Note: The above characteristics data can be obtained within three charge/discharge cycles.
ISO9001 approval, FN: Q3105105131
ISO14001 CTC04912E10302ROM
OHS MS18001 04912S10150ROM
UL approval, FN:MH28204
CE approval, FN:G2M20201-0102-E-16
KS approval, FN:KS C 8519
VDS approval
BS approval
Typical Applications
Fire alarm systems
Solar lighting equipment
Outdoor telecommunication equipment